The office network cannot reach the plant floor. Here is how to show it.
OT network segmentation is only as good as the last time someone tried the path. Which paths to declare at the IT/OT boundary, and how to test them from the office side.
On 28 July 2026 the Australian Signals Directorate published CI Fortify's advice for isolating vital systems, with partner agencies in the United States, the United Kingdom and Canada. It asks operators of critical infrastructure to be able to cut their vital systems off from every other network. It also asks them to test that plan periodically, and to run reachability tests between the critical and non-critical networks, with an alert when a control is ineffective or has been removed.
Most plants have OT network segmentation on paper. There is a firewall between the office network and the plant network, a diagram that shows it, and a rule set somebody reviewed when the line was commissioned. What few plants have is a dated answer to a plain question from an insurer, a customer or the board: could an office PC reach the controllers last Tuesday.
This post is about that boundary, tested from the office side. It covers which paths to write down, how to try them by hand, what to record, and what a one-off test leaves open. The test of a whole isolation plan, step by step, is in how to test an isolation plan.
Why this boundary is the one that gets asked about
Phishing links, USB sticks and stolen passwords land on the office network. The plant network is where a problem stops being an IT incident and becomes a stopped line. The firewall between them is the control that keeps the first from becoming the second.
The best-known example is one where the boundary held. On 7 May 2021 Colonial Pipeline shut 5,500 miles of pipeline for five days after ransomware reached its business network. The CEO told the US Senate the shutdown was to keep the attack from spreading to the operational network, "if it had not already". The GAO later reported no indications that the operational systems had been breached. The 6 a.m. question tells that morning in full.
The lesson for a plant is narrower than it sounds. The design was probably right and the firewalls were probably doing their job. Nobody could show it at six in the morning, so the only safe decision was to stop. Fourteen months later the US pipeline regulator, the TSA, reissued its directive around four outcomes. The first asks that the operational technology system can keep operating safely if the information technology system has been compromised, and vice versa.
The second yard at Lindqvist Marine
Lindqvist Marine builds and refits workboats at one yard and opens a second. The first yard's firewall has been tidy for years: nothing crosses from the office network to the crane and welding-cell controllers, except one engineering workstation on 44818 and 3389.
To save a week, the second yard's rule set is copied from the first. The second yard has no engineering workstation yet, so the integrator points that allow at the whole office subnet to get commissioning finished. The workstation arrives in week 6. The rule stays as it is.
Every review after that reads the rule as "engineering access to the controllers", because that is what its name says. The diagram for the second yard is the first yard's diagram with the addresses changed. Eleven months later, every laptop in the second yard's office can open a remote desktop session to the engineering station's neighbours and speak EtherNet/IP to the cells. Nothing has stopped working, so nothing has been looked at.
Lindqvist Marine is invented.
The paths to write down
A boundary is a short list of connections that must fail and a shorter list that must work. For most plants the first list starts with three ports from two zones. These are from group 05 of the starter policies.
- Office PCs must not reach the Plant network on 502, 44818, 3389 (RDP). Modbus, EtherNet/IP and remote desktop to the engineering workstation are the three paths from the corporate network into operational technology. Segproof names that policy
DENY Office PCs -> PLC-LINE1 +3 targets TCP/502,3389,44818. - Servers must not reach the Plant network on 502, 44818. The corporate server network is where most intrusions spend their first week. A path from it into the industrial protocols is the path from an IT incident to a stopped line.
- The historian or MES server must reach what it reads from. If one server is meant to cross the boundary, give it its own zone and its own Allow. Everything else in the server network keeps the Deny.
The Allow matters as much as the two Denies. A powered-off controller also looks blocked, so one path that is meant to work confirms the targets are listening. It also tells you when a clean-up closes something production depends on.
Practices the list depends on
These are the OT network segmentation best practices that make the list above short enough to keep.
- Zones by what a failure costs. The plant network is its own zone, and so is each line or cell that can run without the others.
- Default deny across the boundary. Every rule that crosses it is an exception with a reason, and "any" appears in none of them.
- One named way in for engineers. Engineering access goes through the designated workstation or a jump host, and never from whichever laptop can reach the subnet.
- Approved paths written down, each with an owner. The Lindqvist rule survived eleven months because its name described the intent and nobody owned the source field.
- A test after every change window. The boundary is usually well designed. The question is whether it is still there after the last three changes.
Network segmentation best practices covers the general version. The control map shows where segmentation sits in eight frameworks, for whoever files the evidence.
Testing the boundary from the office side
Agree the test with whoever owns the plant network before you run anything. Tell them the source machine, the target addresses, the ports and the time. A test that surprises the control room is a bad test, whatever it finds.
Then test from the side the traffic would start from. Sit at an ordinary office PC, on the office VLAN, with no VPN and no admin jump host in the way. For each address and port on your list, attempt one connection and note what happens.
Test-NetConnection 10.50.1.21 -Port 44818
nc -vz -w 5 10.50.1.21 502
One attempt to one named address and one named port is the whole test. It opens a connection and closes it, and sends nothing else. Do not sweep the plant subnet to see what answers. When the boundary holds, the attempt never arrives on the plant side at all, because the firewall drops it first.
A timeout or a refusal is the result you want on a Deny. A connection that opens is a finding, and it goes to the plant network's owner the same hour. The full method, with a test matrix, is in how to test network segmentation.
What to record
Write down enough that somebody else could repeat the test and compare.
| Field | Example |
|---|---|
| Source | OFFICE-PC14, office VLAN, 10.20.5.14 |
| Target | PLC-LINE1, 10.50.1.21 |
| Port | 44818 |
| Expected | Blocked |
| Result | Timed out after 5 seconds |
| When | 18 November 2026, 10:42 |
| Who | Name of the tester, and who on the plant side agreed it |
Keep the rows somewhere that cannot be quietly edited, next to the change record for the window you tested after.
Where a test by hand stops
The table above describes one morning. The rule at Lindqvist's second yard would have passed a test on commissioning day, if the test had been run from the engineering workstation's desk, and failed from every desk after it. A test after each change window narrows the gap. It does not close it, because the changes that open paths are the ones nobody thought were changes to the boundary.
This is the part Segproof does, and the page for plants and utilities shows it against the CI Fortify steps. An agent on an office PC, or on a small computer on the office network, attempts only the connections you declare, as often as every 5 minutes on the paid plan, and never tries an address range. Nothing is installed on the plant side. When a blocked path opens, the alert arrives within 7 minutes on a 5-minute policy, with the agent, the address, the port and the minute. Every result is kept, with a tamper-evident audit log beside it.
Without that, a plant can show a diagram, a rule export and a test from the day somebody last had time. Nobody can show what the declared paths across the boundary were doing on a given day, and that was the record Colonial's control room did not have at 5:55 a.m. A record of declared paths is one input to a decision like theirs, not the decision.